200X Pilot Operated Pressure Reducing Valve
Contact HENGYA for Shipping, delivery, and payments information.
Products Category
Tag list
- 产品描述
-
Design features
- Pilot-operated, self-powered: the line pressure itself drives the main disc, so no external power supply is needed
- Full-bore streamlined flow path, low fluid resistance and high flow capacity
- Downstream pressure held at the value set by the pilot valve spring; the valve closes automatically when outlet pressure exceeds the setting
- Stainless steel pilot head with adjusting screw and locknut, plus inlet and outlet pressure gauges for setting and checking
- Brass strainer in the pilot circuit protects the needle valve and pilot valve from pipeline debris
- Diaphragm separates the control chamber from the line medium, keeping the pilot circuit clean
How it works
The 200X is a hydraulically operated control valve made up of a main valve and an auxiliary pilot control system: pilot piping, a needle valve, a ball valve, a pilot valve and two pressure gauges. Water pressure in the pipeline moves the main valve disc up and down, changing the opening of the valve port and regulating the downstream pressure. The pilot circuit sets the pressure acting on the diaphragm, which positions the main disc. When downstream pressure reaches the set value, the valve throttles and holds outlet pressure constant.
Technical specification
Model 200X Nominal size DN50 - DN600 Nominal pressure PN10 / PN16 / PN25 Body material Ductile iron QT450-10 Working medium Water Working temperature 0 - 80 °C Connection Flanged, ISO 7005 / EN 1092-2 (PN10 / PN16 / PN25) Pressure test Shell 1.5 x PN, seal 1.1 x PN to EN 12266-1 Pressure ratings and adjustable outlet range
Parameter PN10 PN16 PN25 Nominal pressure (MPa) 1.0 1.6 2.5 Shell test pressure (MPa) 1.5 2.4 3.75 Seal test pressure (MPa) 1.1 1.76 2.75 Maximum inlet pressure (MPa) 1.0 1.6 2.5 Outlet pressure adjustable range (MPa) 0.09 - 0.8 0.10 - 1.2 0.15 - 1.6 Outlet pressure is set at the pilot valve to the ordered value before dispatch. The DN100 unit shown in the photographs is set to 0.75 MPa; the adjustable range for each pressure rating is given in the table above.
Materials of construction
Body / Bonnet Ductile iron QT450-10 Disc / Clamp plate Ductile iron QT450-10 Stem 20Cr13 martensitic stainless steel (AISI 420) Seat DN50 - DN200: stainless steel 304; DN250 - DN600: brass Diaphragm / Gasket EPDM Spring Stainless steel 304 Pilot valve / Needle valve / Ball valve / Elbow / Strainer Brass Bottom plate Carbon steel Hex bolt / Nut Stainless steel 201 Dimensions (mm)
DN L D2 D1 n - dia. T F D 50 215 165 125 4-19 19 3 99 65 235 185 145 4-19 19 3 118 80 275 200 160 8-19 19 3 132 100 306 220 180 8-19 19 3 156 125 306 250 210 8-19 19 3 184 150 375 285 240 8-23 19 3 211 200 430 340 295 8-23 / 12-23 20 3 266 L face-to-face, D2 outside diameter of flange, D1 bolt circle diameter, n-dia. number and diameter of bolt holes, T flange thickness, F raised face height, D overall height. DN250 and above to drawing.
Installation
- Install horizontally with the bonnet facing upwards; other orientations also work
- Clean all debris out of the pipeline before fitting
- Follow the flow-direction arrow on the body
- No pipeline stress may act on the body or its internals after installation
- Fit a gate valve and a strainer upstream, and a gate valve downstream, so the valve can be serviced
- Flush the system thoroughly before admitting water; fit a bypass on important supply lines
Setting the outlet pressure
- Close the upstream isolating valve, open the downstream valve to release pressure, wait until it falls to zero, then close it
- Turn the pilot adjusting screw to its uppermost position and open the needle valve about half a turn
- Open the upstream isolating valve slowly and fully
- Screw the pilot adjusting screw down gradually; outlet pressure rises. Lock the screw when the required set point is reached
- Adjust in small increments while watching the downstream gauge. Pressure can only be set upwards from a lower value - if set too high, repeat from step 1
Standards and certification
Flange dimensions ISO 7005 / EN 1092-2 Pressure testing EN 12266-1 Quality management ISO 9001, certificate no. 05325Q30683R1S Environmental management ISO 14001, certificate no. 05325E30489R1S Occupational health and safety ISO 45001, certificate no. 05325S30455R1S ISO 9001, ISO 14001 and ISO 45001 certificates are held by Hebei Hengya Technology Co., Ltd. and are valid until 19 October 2028.
Applications
- Water supply networks where a high-pressure main feeds a lower-pressure distribution zone
- Building installations requiring a stable reduced pressure
- Fire-fighting water supply systems
- Industrial water supply and process lines
Contact Us
200X Pilot Operated Pressure Reducing Valve
Contact HENGYA for Shipping, delivery, and payments information.